        Products Micro module data center11 Micro module data center33
        Double row micro module (intelligent column head cabinet)

        Basic Features

        Intelligent column header cabinet is a distribution cabinet that comprehensively collects all energy data for the energy terminal of the data center computer room. It provides high-precision measurement data for the terminal energy monitoring system, reflects the power quality data in real time through the display unit and uploads it to the background dynamic environment control system through digital communication, so as to achieve effective management of the real-time monitoring and operation quality of the entire distribution system, help users optimize the network data center, strengthen energy consumption management, improve the server operation efficiency, and provide reliable guarantee for the all-round green data center.


        Technical Specifications

        Ratedpower

        60KW

        100KW160KW

        Ratedcurrent

        100A160A

        250A

        Ratedvoltage

        380VAC/50Hz

        Power supply ? system

        Three phase five ? wire (TN-S)

        Output branch

        Up to 108 single ? routes, up to 54 dual routes

        Power display

        A

        B
        C3 phase LED ? display

        Parameter ? display

        7-inch touch ? screen

        Main road parameters

        Three-phase ? voltage, three-phase current, frequency, status, bus temperature ? (customized), harmonics, load percentage, electrical energy

        Active power, ? reactive power, apparent power, power factor

        Branch ? parameters

        Phase voltage, ? phase current, load percentage, electrical energy, active power, power ? factor, frequency, state, temperature (customized)

        Bus alarm

        Overvoltage, ? undervoltage, phase loss, loss, current exceeding high limit, current ? exceeding low limit, frequency fault, overtemperature

        Branch alarm

        Overcurrent, ? instantaneous overcurrent, current exceeding high limit, current exceeding ? low limit, switch opening, switch closing

        Communication? interface

        RJ45

        withstanding ? voltage

        2000VAC/min

        Environmental ? conditions for use

        Temperature ? range -5 ~+40 , humidity range O%~90% (without ? condensation),

        Altitude less ? than 2000M (derating should be considered when altitude is 1000M)

        Executive ? standards

        GB7251-1

        GB7251-3