<th id="geemy"><nav id="geemy"></nav></th>
<samp id="geemy"><tbody id="geemy"></tbody></samp>
    • <ul id="geemy"></ul>
      • <th id="geemy"><menu id="geemy"></menu></th>
        <strike id="geemy"></strike>
        DP series low frequency online UPS 1 ~ 20 kVA

        Product profile

        Real online UPS, pure sine wave output, applying dual conversion pure online IGBT technology. Small size, low noise, strong and durable.


        Basic Features

        ◆ Real online UPS, pure sine wave output, the application of dual conversion pure online IGBT technology, small volume, low noise, durable.

        ◆ LCD display panel, through the LCD selection switch, convenient to check the UPS working state: whether the battery is normal, input / output voltage value, input / output frequency value, battery voltage value, output power and other important parameters.

        ◆ The input voltage is particularly wide, allowing 25% of the change can be full load work, reduce the opportunity of battery discharge, effectively extend the life.

        ◆ The charging current is 1~10A adjustable, which meets the charging requirements of the long-time power supply system, especially designed for China's power grid.

        ◆ Special static switch design, with zero output interruption during power grid failure, and a bypass output time of<2 ms during UPS failure.

        ◆ Very strong load capacity, 125% load online work for 15 minutes, load more than 125% online work for 60 seconds to bypass, load more than 150%3 seconds to bypass output, overload phenomenon disappeared after the automatic restart operation.

        ◆ Output short circuit protection to ensure that the UPS is not damaged by short circuit of external load.

        ◆ Temperature control and protection, set the internal temperature, protection component life.

        ◆ Has a powerful load start function, can be directly turned on in the battery state, supply output.

        ◆ Input / output is completely isolated, with strong anti-interference ability, strong impact resistance, safe and reliable.

        ◆ Provide a dual-machine thermal backup power supply system.

        ◆ Unique sound alarm to remind the user to notice the working state of the UPS.

        ◆ Built-in maintenance bypass, can achieve online maintenance.

        ◆ RS232 communication interface, with optional remote monitoring function.


        Technical Specifications


        Model

        DP1kVA

        DP2kVA

        DP3kVA

        DP6kVA

        DP10kVA

        DP15kVA

        DP20kVA

        Capacity

        0.8kW

        1.6kW

        2.4kW

        4.8kW

        8kW

        12kW

        16kW

        Input voltage

        220/230VAC±25%

        Input frequency

        50/60Hz±10%

        Output voltage

        220VAC±1%

        Output frequency

        50/60Hz±0.5% (battery mode, unlocked)

        Voltage error

        ±2%

        Temporal reaction

        ±4% (100% load)

        Wave form

        Sine wave THD<3%

        Overload capacity

        125% load working online for 15 minutes, load over 125% online ? working for 60 seconds to bypass, load over 150%3 seconds to bypass output

        Wave peak ratio

        3:1

        Battery type

        Enclosed maintenance-free lead-acid battery

        DC voltage (extended time with external battery)

        48VDC

        96VDC

        192VDC

        Battery capacity of standard device

        12V7AH×4

        12V7AH×8

        12V7AH×16

        Charging current

        1~10A adjustable

        Efficiency

        90%

        Transfer time

        Zero ms for mains failure ?and<2ms for bypass switch

        Protection function

        Over-current, overvoltage, low voltage, short circuit, battery ? overcharge, overheat protection, etc

        EMC

        EN62040-2:2006; EN61000-3-2:2006+A1:2009+A2:2009

        Power loss alarm

        1 time/4s, keep 90s

        Battery low-voltage alarm

        1 second/ 1 time (battery discharge to protection voltage, UPS automatically?

        shutdown, automatically boot when mains recovery)

        Overload alarm

        Continuous calling (hold the jump bypass for 60 seconds, automatic recovery?

        after load reduction)

        Failure warning

        Continuous beep

        LED display

        main input/ bypass/ inverter/ low battery/ overload/ fault

        LCD display

        UPS status: input/ output/ battery voltage, input/ output frequency, load amount

        Communication interface

        Rs-232/ dry contact, support remote monitoring and management

        Running temperature

        0℃~40℃

        Running height

        Elevation<1000 m (1% for every 100 m, maximum 4000 m)

        Humidity

        0%~90% (no condensation)

        Noise

        <58dB

        Dimension (D×W×H) mm

        520×180×400

        595×215×420

        590×245×530(730)

        685×360×825

        Reference Weight (kg)

        Extended time

        30

        41

        52

        48

        69

        130

        155

        Standard

        41

        58

        69

        85

        110

        147

        172


        Note: Customizable output power PF=0.9.