        D Series High-Frequency Online UPS 1~3kVA

        Product profile

        Digital Series UPS adopts dual-conversion online design, intelligent MCU / DSP precision control; when mains is interrupted or restored, UPS transfer time is zero between main mode and battery mode, effectively ensuring the reliability of load operation.


        Basic Features

        Online-type design, zero transfer

        Digital Series UPS adopts dual-conversion online design, intelligent MCU / DSP precision control; when mains is interrupted or restored, UPS transfer time is zero between main mode and battery mode, effectively ensuring the reliability of load operation.

        High quality sine waves (THD<3%, linear) can be output either in mains mode or battery mode to provide the best power supply for the load.

        energy-efficient

        PFC power factor correction design and IGBT transformation technology are adopted, the input power factor is 0.99, and the overall efficiency is 90%.


        Detection and self-protection function

        Digital Series UPS can simulate the power failure and enter the battery mode. This function can be executed at any time through "self-test button" on the panel, or with random monitoring software; perfect self-protection function, peak current and short circuit protection design, super load impact resistance.


        TVSS function

        Namely, TRANSIENT VOLTAGE SURGE SUPPRESS burst wave voltage protection function. Utend FAX. TELEPHONE, MODEM network and other conversion protection.


        DC start function

        In the state of mains power failure, if UPS is needed to start the computer or other load equipment, Digital series UPS can be directly started in battery mode, making the use of UPS more convenient and reliable.


        Automatic bypass / manual bypass / maintenance bypass (optional)

        In addition to the automatic bypass function, the Digital series UPS also has the function of manually setting the bypass on the panel keys; when necessary, the manual maintenance bypass can also be optional for online maintenance.


        Optional lightning protection function

        Optional D class lightning protection device, with surge protection, lightning protection design, effectively protect the equipment from lightning interference.


        EPO emergency shutdown function (optional)

        Optional EPO switch to realize emergency shutdown of UPS.


        Rich and humanized LCD / LED content display

        UPS operating status (mains mode / battery mode / bypass mode), input and output, battery power, load size, and failure code, etc., at a glance.


        Extended time type power supply design

        Digital Series UPS fully provides extended time machines for users to choose from. The appropriate battery pack can bring the discharge time of the UPS to about 8 hours to meet the requirements of different power grid environments. Digital Series UPS extended time machine in addition to the discharge time to extend the battery recharge capacity is also very strong, can provide about 3 ~ 4A initial charging current (can also be selected according to user needs, a larger charging current).


        Can be used with a generator

        The ultra-wide input voltage and frequency range enable Digital series UPS to be used with mainstream brand generators to extend the use time and effectively remove the impure power generated by the generator, providing safe and stable power supply for the load.


        Adaptable perceptual load

        Digital Series UPS allows for sensitive load.


        Random monitoring software

        Rs 232 communication interface (optional USB interface), random monitoring software, to realize the intelligent management of UPS by users.


        Equipped with Intelligent Slot intelligent slot for remote monitoring (optional)

        Digital Series UPS is equipped with-Intelligent Slot smart slot, users can choose SNMP network card to realize centralized monitoring and remote monitoring and other functions.


        Technical Specifications


        Model

        D1K

        D1KS

        D2K

        D2KS

        D3K

        D3KS

        Rated capacity?

        (PF=0.9)

        1kVA/0.9kW

        2kVA/1.8kW

        3kVA/2.7kW

        Input

        Voltage

        120Vac~300Vac (single-phase secondary line+ground wire)

        Frequency

        50/60Hz±10%

        Output

        Voltage

        220/230±1%Vac

        Frequency

        Synchronized with input (mains mode), 50/60Hz±0.5% (battery mode)

        Discharge waveform

        Pure sine wave

        Transfer time

        Zero interruption

        Built-in battery (12V)

        7Ah/9Ah×2


        7Ah/9Ah×4

        -

        7Ah/9Ah×6


        External battery DC voltage nominal


        36Vdc


        72Vdc


        96?Vdc

        Battery type

        Valve-controlled lead-acid maintenance-free storage battery

        Overload capacity

        105% -120%, to?bypass?after?10 seconds;
        120-140%,?to?bypass?after?200ms;
        ? ?140-150%, to?bypass?after?200ms, and then shutdown?10 seconds later;
        ? > 150% shutdown?immediately

        Load peak ratio

        3?:1(?max)

        Distortion rate(full load)

        <3%(linear load)

        <5%(nonlinear load)

        Communication interface

        Rs-232 interface (optional USB interface)+SNMP smart slot

        Working temperature

        0℃~40℃

        relative humidity

        0~90%(no condensation)

        Dimension(D×W×H)

        405×145×220mm

        465×196×345mm

        Net weight (kg)

        10.5/11.4

        6.5

        18.5/20.3

        12

        23.5/26.2

        12.5

        Compliance with standards

        GB/T14715-2017; YD/T1095-2018; EN62040-1:2008+A1:2013; EN62040-2:2018

        Remarks:

        1. Select the rated capacity (output power) PF = 0.8.

        2. The model with "S" is a extended time model, and the battery should be configured according to the external battery DC voltage, and the DC voltage of D 2 KS external battery can be selected as 96 Vdc.

        3. Other internal battery configurations are available in the following models:

        D1K: 12V7Ah/9Ah×3 ; D2K: 12V7Ah/9Ah×6 ; D3K: 12V7Ah/9Ah×8 ;

        4. Load in high altitude = rated power x reduction coefficient

        Altitude (m)

        1000

        1500

        2000

        2500

        3000

        3500

        4000

        4500

        5000

        Frequency reduction coefficient

        100%

        95%

        91%

        86%

        82%

        78%

        74%

        70%

        67%

        * The above parameters may be adjusted and changed, please refer to the physical object. If the UPS is used above 1000m, decreasing rated output must be used, refer to the table above.